Circuit Breaker Size Calculator

Determine the correct circuit breaker size for continuous, non-continuous, or mixed loads per NEC requirements.

Results

Visualization

How It Works

Circuit breakers protect wiring from overcurrent. NEC requires continuous loads (running 3+ hours) to be sized at no more than 80% of the breaker rating, meaning the breaker must be 125% of the continuous load.

The Formula

Continuous: Breaker ≥ Load × 1.25
Non-continuous: Breaker ≥ Load
Mixed: Breaker ≥ (Continuous × 1.25) + Non-continuous

Variables

  • Load — The actual current draw of the circuit in amperes
  • 1.25 — NEC 210.20 multiplier for continuous loads (80% rule inverse)
  • Breaker — Next standard breaker size above the adjusted load

Example

A 16A continuous load: 16 x 1.25 = 20A adjusted load. The next standard breaker size is 20A. Required wire: 12 AWG copper.

Tips

  • Continuous loads run for 3 hours or more (lighting, HVAC, electric heaters).
  • Standard breaker sizes are: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100A.
  • Always match wire gauge to the breaker size, not just the load.
  • Some 100% rated breakers can carry continuous loads at full rating but are more expensive.
  • When in doubt, size up to the next breaker and wire gauge for added safety margin.